Look at the first cycles of a fault or switching

What it tells you. An electromagnetic transient (EMT) simulation shows the voltage and current of each phase, sample by sample. It covers the first cycles after a fault or a switching operation. Use it to see the peak of a fault current, the voltage peaks a switching operation causes, and how an unbalanced fault looks.

Warning. EMT is not a grid code compliance tool. Every source keeps the voltage it had in the load flow, no rotor moves and no control acts. The results mean something only for the first cycles. Use the stability simulation for swings over seconds.

Before you start

Check that the network has the data below. Select an element to see its data in the inspector.

DataWhere to enter it
Complete load flow data, because the simulation starts from the load flowSee Run a load flow
Machine Subtransient reactance xd″ and Stator resistanceInspector, Short circuit
External grid Short-circuit power max, R/X ratio max, X0/X1 ratio and R0/X0 ratioInspector, Short circuit
Line Length, Reactance X′ and Susceptance B′, which set how a line behaves in timeInspector, Basic data
For unbalanced faults: line Zero-sequence R0′, Zero-sequence X0′ and Zero-sequence B0′Inspector, Short circuit
For unbalanced faults: transformer Vector group, Zero-sequence uk0 and neutral earthingInspector, Basic data and Short circuit
The events: faults, clearings and switching, with their timesEMT events dialog, described below
Simulation time, Time step and Line modelStudy case, under EMT simulation

A line without zero-sequence data takes its positive-sequence values, and the report says so. Machines are unearthed. An external grid is unearthed when its X0/X1 ratio is 0. See zero-sequence data.

Set up the study

Each event has a time in milliseconds, a type and an element.

  1. Select the Calculate tab.
  2. Under Dynamics, select EMT events. The Study case dialog opens at EMT events.
  3. Select Add EMT event.
  4. In Time (ms), enter when the event happens.
  5. In Event, choose Fault at, Clear fault at, Trip or Close.
  6. In Element, choose a busbar for a fault or a clearing. Choose a line, transformer, machine, external grid, load or shunt for a trip or a close.
  7. For a fault, choose its type in Fault. The types are Three-phase, Line to line, Two phases to earth and Line to earth. Enter a fault resistance in R Ω, or leave it empty for a bolted fault.
  8. Repeat steps 3 to 7 for each event.
  9. Select Apply.

Events act at the nearest time step. The 4 event types behave as follows.

To add a fault quickly, right-click a busbar and select Add fault to EMT simulation. This adds a line-to-earth fault after 1 cycle and clears it 5 cycles later.

To change the other settings, press Ctrl+, to open Study case, then scroll to EMT simulation.

SettingWhat it does
Simulation timeSets how long to simulate. The default is 0.2 s.
Time stepSets the step in microseconds. The default is 50 µs. Shorten it for travelling waves on short lines and cables.
Line modelChooses Travelling waves where they fit the step, which is the default, or π sections everywhere.

The method is Dommel's method. See the engine description.

Run it

  1. On the Calculate tab, select EMT, or press Alt+W.
  2. Wait for the progress bar in the status bar to finish.

The EMT tab opens in the results panel. The Output tab logs the highest voltage and the peak fault current. It also warns about any event that had no effect.

To stop a run, press Ctrl+.

Read the results

The top of the EMT tab shows a pill and a summary. The pill gives the time simulated, such as 200 ms simulated. The summary gives the Step, the Highest voltage in p.u. of crest, the Peak fault current and the Time.

Use the buttons on the right of the tab to switch between 6 views.

ViewWhat it shows
WaveformsThe 3 phases of a voltage or current against time
BusbarsBusbar, Un, Peak voltage, Peak as a share of the nominal crest, At, Lowest RMS and Highest RMS
BranchesBranch, Model, Peak current and At. The model is Travelling wave, π section or Transformer.
SourcesSource, Peak current and At
FaultsBusbar, Fault, From, Out, Peak current, At and RMS, last cycle
SwitchingTime, Kind and What happened, for each event and each pole that opened

Times in the tables are in milliseconds. The Sources and Faults buttons appear only when the run has sources or faults.

Read a waveform

  1. In Waveforms, select a busbar or branch on the diagram. Its phases are plotted.
  2. To plot something else, choose a quantity in Quantity plotted. The choices are Busbar voltage, Branch current, Source current and Fault current.
  3. To hide a phase, select its Phase button.
  4. To zoom in, drag across a time range, or select Zoom in on time.
  5. To see the whole run again, double-click the plot, or select Show the whole run.

Read the numbers

The crest is the nominal peak of the phase-to-earth voltage. A Peak of 1.0 p.u. is the normal peak. The RMS value is taken over 1 cycle, after the first cycle.

The Busbars table highlights a Peak above 1.2 p.u. in amber and above 1.5 p.u. in red. Its filters are Peak above 1.2 p.u. and RMS below 0.9 p.u.

A fault current is the sum of a steady part and a decaying DC offset. The Peak current includes the offset. RMS, last cycle is the RMS of the largest phase over the last full cycle before the fault went out.

Check your results

Warning. Switching overvoltages can depend on the step. Check them with a shorter Time step before you quote a peak.

If something goes wrong

What you seeWhat it meansWhat to do
Event, no effect in Switching, or a warning in OutputAn event did nothing, for example a clearing with no faultCheck the element and time of the event in EMT events.
A warning that a pole did not reach a current zeroA DC offset kept the current from crossing zero, so the pole stayed closedRaise Simulation time, or move the event.
Out shows to the endThe fault has no Clear fault at eventAdd a clearing event.
EMT simulation cannot run, and a message about a lineA line joins busbars with different nominal voltagesReplace the line with a transformer.
EMT simulation failed, and a message about a zigzag windingThe EMT model does not support zigzag windingsChange the transformer's Vector group for this study.
An event never happensIts time is after the Simulation timeMove the event, or raise Simulation time in Study case.
The pill Calculated before the last editYou changed the network after the runRun EMT again.

Try it on the IEEE 14-bus sample

  1. Select the Help tab.
  2. Under Samples, select IEEE 14-bus system.
  3. Select EMT events. The sample has 3 events.
  4. Read them. A three-phase Fault at Bus 4 is at 20 ms. Clear fault at Bus 4 and Trip Line 4-5 are both at 100 ms.
  5. Select Cancel, then select EMT.
  6. Read the summary. The Highest voltage is 1.74 p.u. at Bus 9. The Peak fault current is 12.80 kA.
  7. In Waveforms, select Bus 4 on the diagram. The 3 voltages fall to 0 at 20 ms.
  8. Select Faults. The fault lasts from 20.00 ms to 108.45 ms. The Peak current is 12.802 kA at 27.55 ms. RMS, last cycle is 5.865 kA.
  9. Select Switching. The 12 rows show the 3 events and 9 poles opening. Each phase of the fault and of Line 4-5 opens at its own current zero, between 102.65 ms and 108.45 ms.
  10. Select Busbars. Bus 9 has the highest Peak at 1.742 p.u., at 105.05 ms. That is after clearing starts, not during the fault.

Check the numbers against the short circuit study. For a three-phase fault at Bus 4, Ik″ is 6.157 kA and ip is 13.650 kA. The EMT values are about 5 % and 6 % lower.

Try other fault types

Change the Fault of the first event to see the peak current at Bus 4.

FaultPeak currentRMS, last cycle
Three-phase12.802 kA5.865 kA
Line to line11.290 kA5.124 kA
Two phases to earth12.048 kA5.709 kA
Line to earth3.640 kA2.481 kA

The earth fault is small because the sample's machines are unearthed.

Try it on the Riverside sample

  1. Under Samples, select Riverside distribution.
  2. Select EMT events. The sample has a Line to earth fault at Hilltop at 20 ms and its clearing at 80 ms. It trips the Capacitor bank at 120 ms and closes it at 160.1 ms.
  3. Select Cancel, then select EMT.
  4. Select Busbars, then select Peak above 1.2 p.u. The list has one row: Mill Lane at 1.236 p.u., at 160.40 ms. That is 0.3 ms after the capacitor bank closes.
  5. Select Faults. The Peak current is 6.210 kA at 33.75 ms. RMS, last cycle is 4.222 kA.

The RMS value lies between the minimum and maximum Ik″ of a line-to-earth fault at Hilltop: 3.823 kA and 4.450 kA.

Now check the step. Open Study case and set Time step to 25 µs, then run it again. The fault peak stays at 6.210 kA. The highest voltage rises to 1.38 p.u. at Station Road. At 10 µs it is 1.63 p.u.

The cables here are short, so a coarse step treats them as π sections. A shorter step models them as travelling waves, and the switching peak changes. This is why you should check a switching overvoltage against a shorter step.