Run a load flow

What it tells you. A load flow finds the steady state of your network. It gives the voltage at every busbar and the power in every line and transformer. Use it to check that voltages stay in their band, that nothing is overloaded and how much power the network loses.

Before you start

Check that the network has the data below. Select an element to see its data in the inspector on the right. The inspector groups data under Basic data, Load flow, Short circuit, Stability and Diagram.

DataWhere to enter it
Busbar Nominal voltageInspector, Basic data
Busbar Lower voltage limit and Upper voltage limit, in per unitInspector, Load flow
Line Length, Resistance R′, Reactance X′, Susceptance B′ and Rated currentInspector, Basic data
Transformer Rated power, Rated voltage HV, Rated voltage LV, Short-circuit voltage and Copper losses (resistive part)Inspector, Basic data
Transformer No-load current, Iron losses and tap changer settingsInspector, Load flow
Machine Control mode, Active power, Voltage setpoint, Reactive power minimum and Reactive power maximumInspector, Load flow
External grid Voltage setpoint and Voltage angleInspector, Load flow
Load Active power and Reactive powerInspector, Load flow
Shunt Reactive power per section and Sections in serviceInspector, Load flow

Each connected part of the network needs a source. That is an external grid, or a machine whose Control mode is Reference.

A machine's Control mode sets what it holds. PV holds active power and voltage. PQ holds active and reactive power. Reference sets the angle and balances the system.

Set up the study

  1. Select the Calculate tab.
  2. Under Steady state, switch on the options you want: Recalculate on edit, Respect Q limits and DC start.
  3. To change other settings, press Ctrl+, to open Study case.
  4. Scroll to the Load flow heading and change the settings you need.
  5. Select Apply.

The settings you will use most are in this table.

SettingWhat it does
Power mismatch toleranceSets how small the power imbalance must be before the solution is accepted. The default is 0.001 MVA.
Maximum iterationsSets how many steps the solver may take. The default is 30.
Respect reactive power limitsHolds a machine at its reactive limit, instead of its voltage setpoint, when it reaches that limit. Off by default.
Start from a DC load flowTakes the starting angles from a DC load flow. It helps meshed networks with phase-shifting transformers to converge. On by default.
Load scalingScales every load, as a percentage. The default is 100 %.
Tap changers regulate voltageLets transformer tap changers move to hold a busbar voltage. Off by default.
Phase shifters regulate flowLets phase-shifting transformers move to hold a power flow. Off by default.
Switched shunts regulate voltageLets switched shunts add or remove sections to hold a voltage. Off by default.
Share each island's imbalance amongChooses which machines take up the difference between generation and load.

The ribbon switch Respect Q limits is the setting Respect reactive power limits. DC start is Start from a DC load flow. For how the solver works, see the engine description.

Run it

  1. On the Calculate tab, select Load flow. You can also press Alt+L or Ctrl+Enter.
  2. Wait for the progress bar in the status bar to finish.

The Load flow tab opens in the results panel, and the diagram shows the results. The Output tab logs a summary, such as the iterations and the highest loading.

To stop a calculation that takes too long, press Ctrl+. or select Cancel calculation on the Calculate tab.

With Recalculate on edit on, the load flow runs again after each change you make. It starts only after you have run it once.

Read the results

The top of the Load flow tab shows a summary:

Use the buttons on the right of the tab to switch between its tables.

TableWhat it lists
BusbarsBusbar, Type (Ref, PV or PQ), U in kV, u in p.u., Angle, P injected and Q injected
BranchesBranch, Type, Loading in %, P from, Q from, P to, Q to, I max and Losses
Machines and loadsElement, Type, P, Q and a Note such as At upper Q limit
ControlsEach tap changer, phase shifter or switched shunt that moved: Before, After, Moved and Range
AreasEach area's Net export against its Target
WarningsWarnings and De-energised busbar rows

The tables Controls, Areas and Warnings appear only when they have something to show. The first 3 short warnings show as pills instead of a table.

On the diagram, each busbar's result box shows its voltage and angle. Each branch shows the power at both ends and its loading. Colours show loading from 0 % to 100 % or more. Busbars outside their band have their own colours.

To show only the rows that need attention, use the filters above the table. See Work with results.

Check your results

Use these checks before you rely on a result.

To check your results against another tool, see Check PowerStudio against your own tool.

If something goes wrong

What you seeWhat it meansWhat to do
A red pill, such as "No convergence after 30 iterations", that names a busbarThe solver stopped with a large mismatch near that busbarCheck the loads and data around that busbar. Try a lower Load scaling. Switch Start from a DC load flow on or off.
A Load flow cannot run message about a line that joins busbars with different nominal voltagesA line connects 2 voltage levelsReplace the line with a transformer.
A Nothing to calculate messageThe network has no busbarsDraw a network or open a sample.
De-energised busbars in the Output tabA part of the network has no external grid or reference machineConnect it to a source, or set a machine in it to Reference.
A machine says At upper Q limit or At lower Q limitIt cannot hold its voltage with the reactive power it hasChange the setpoint, the limits or the network.
The pill Calculated before the last edit, and old on the tabYou changed the network after the calculationRun the load flow again.

A load flow starts from the last one that converged. If it does not converge from that start, PowerStudio tries again from the usual start before it reports a failure.

Try it on the IEEE 14-bus sample

The IEEE 14-bus sample is a 132/33/11 kV transmission network with 5 machines.

  1. Select the Help tab.
  2. Under Samples, select IEEE 14-bus system.
  3. Select the Calculate tab, then select Load flow.
  4. Read the summary. The pill says Converged in 2 iterations. Generation is 272.39 MW, Load is 259.00 MW and Losses are 13.393 MW.
  5. Check the balance. 259.00 MW plus 13.39 MW is 272.39 MW.
  6. In the Busbars table, select Outside band. It lists 3 busbars: Bus 6 at 1.0700 p.u., Bus 7 at 1.0615 p.u. and Bus 8 at 1.0900 p.u.
  7. Select Bus 8 to see its data. Its Upper voltage limit is 1.06 p.u., and the machine there holds 1.09 p.u.
  8. In the Branches table, look at Loading. The highest is Transformer 5-6 at 76.4 %, then Line 1-2 at 72.5 %. No branch is above 90 %.

The Riverside sample is a 110/20/0.4 kV distribution network. Under Samples, select Riverside distribution. Its load flow also converges in 2 iterations. Generation is 26.61 MW, Load is 26.32 MW and Losses are 0.293 MW.

Read more