PowerStudio

Guide · 1.2.0

Enter element data

Every element in your network carries data: a line has its impedance, a transformer its ratings, a machine its set points and reactances. This chapter shows you where to enter that data, how to change many elements at once, and which data each study reads.

A new element starts with typical values, so you can run a study straight away. The results are only as good as the data, so replace the typical values with your own before you rely on a result. Data you import comes from the source model. PowerStudio fills any gap with typical values and lists them in the import notes.

Before you start

Draw or import your network first. Build your network shows you how.

Keep your data sheets to hand. Each field in PowerStudio shows its unit, so check that your values use the same one. For example, a line's impedance is in Ω/km and a transformer's short-circuit voltage is in %.

Open an element's data

  1. Select the element on the diagram, in the model tree, or from the command palette (Ctrl+K).
  2. Look at the inspector on the right. If you cannot see it, select Inspector on the View tab.

The inspector shows the data in up to 5 groups. Each group opens and closes when you select its heading.

GroupWhat it holds
Basic dataName, connections, whether the element is in service, ratings and the impedance in the positive sequence
Load flowSet points, limits, loads, taps and controls
Short circuitData for fault currents: subtransient reactances, zero-sequence impedances, earthing and source type
StabilityRotor model, inertia, and the exciter, governor and stabiliser of a machine
DiagramPosition, bar length, side, route and labels

A group appears only if the element has fields in it. A field appears only when it applies. For example, Voltage target shows only when Automatic tap control is on.

To see what a field means, hover over its name.

Enter a value

  1. Select the field.
  2. Type the value.
  3. Press Enter.

If the value is outside its allowed range, PowerStudio refuses it. It tells you why below the field and keeps the old value.

Every change is 1 step you can undo with Ctrl+Z. With Recalculate on edit on, the load flow runs again after each change, once you have run it.

To check your changes, select an empty part of the diagram. The inspector then shows the network's Name, Base power, Frequency and Description. Set the Frequency to 50 Hz or 60 Hz to match your system. The EMT simulation uses it.

Enter data for each kind of element

Busbars

Lines

Enter the data per kilometre: Resistance R′ (Ω/km), Reactance X′ (Ω/km) and Susceptance B′ (µS/km), with the Length (km) and the number of Parallel systems.

Rated current (kA) sets the line's loading. If you enter 0, the line has no rating and PowerStudio does not report its loading. The earth-fault data are under Short circuit: Zero-sequence R0′, Zero-sequence X0′ and Zero-sequence B0′.

Transformers

Machines

External grids

Enter the Voltage setpoint and Voltage angle under Load flow. Under Short circuit, enter Short-circuit power max and Short-circuit power min, the R/X ratios, and the zero-sequence ratios X0/X1 ratio and R0/X0 ratio.

Loads

Enter the Active power and Reactive power at nominal voltage. The constant impedance and constant current shares say how the power varies with voltage. A load that is an asynchronous motor feeds maximum short-circuit currents. Select Asynchronous motor under Short circuit and enter its motor data.

Shunts

Enter the Reactive power per section: positive for a capacitor and negative for a reactor. Then enter the Sections in service and Sections installed.

Enter data for many elements at once

The Data tab shows every element of 1 kind as a table, like a spreadsheet.

  1. In the results panel, select the Data tab.
  2. In the list at the left of the toolbar, choose the kind of element, such as Busbars.
  3. To narrow the rows, type in Filter by name or identifier. You can also select Selected on the diagram.
  4. Select a cell, then type a value and press Enter.

Each column is a field from the inspector, without the Diagram group. A dash means the field does not apply to that element.

To change several elements together:

  1. Select the rows. Hold Shift or Ctrl to select more than 1, or press Ctrl+A to select all.
  2. Select a cell in the column to change.
  3. Type the value and press Enter.

To paste a block from a spreadsheet:

  1. Select the first cell to fill.
  2. Press Ctrl+V.

PowerStudio fills cells to the right and down. It pastes the whole block or none of it. If a value does not fit, a message names the element and the reason, and nothing changes. Ctrl+Z undoes a paste or a change to many rows as 1 step.

The machine's Exciter, Governor and Stabiliser are edited in the inspector, not in the sheet.

Find out which data each study needs

Every study reads the network's connections and the in-service state of each element. The table shows the data it reads beyond that. To check the data for a study, open each group in the inspector and check the fields listed.

StudyElementFields to checkInspector group
Load flowBusbarsNominal voltage, Lower voltage limit, Upper voltage limitBasic data, Load flow
Load flowLinesLength, Resistance R′, Reactance X′, Susceptance B′Basic data
Load flowTransformersRated power and voltages, Short-circuit voltage, Copper losses (resistive part), Vector group, no-load current, iron losses, tap changerBasic data, Load flow
Load flowMachinesControl mode, Active power, Voltage setpoint, reactive power limitsLoad flow
Load flowExternal gridsVoltage setpoint, Voltage angleLoad flow
Load flowLoadsActive power, Reactive powerLoad flow
Load flowShuntsReactive power per section, Sections in serviceLoad flow
ContingencyLinesRated currentBasic data
ContingencyTransformersRated power, Rated power limits loadingBasic data
ContingencyBusbars and machinesVoltage limits, and the reactive power limits if the study case respects themLoad flow
Short circuitExternal gridsShort-circuit power max and min, R/X ratio max and minShort circuit
Short circuitMachinesShort-circuit source, Subtransient reactance xd″, Stator resistance, Voltage regulation range, Unit transformerShort circuit
Short circuitTransformersRated power and voltages, Short-circuit voltage, Copper losses (resistive part), Vector groupBasic data
Short circuitLinesResistance R′, Reactance X′Basic data
Short circuitLoadsAsynchronous motor and its data, for maximum currentsShort circuit
Short circuit, earth faults onlyLinesZero-sequence R0′, Zero-sequence X0′, Zero-sequence B0′Short circuit
Short circuit, earth faults onlyTransformersZero-sequence uk0, Zero-sequence uR0, neutral earthingShort circuit
Short circuit, earth faults onlyExternal gridsX0/X1 ratio, R0/X0 ratioShort circuit
StabilityMachinesRotor model, Inertia constant, Damping, Transient reactance xd′, Exciter, Governor, StabiliserStability
StabilityMachines, round rotorThe synchronous and transient reactances and time constants, and the saturationStability
StabilityMachines, round rotorSubtransient reactance xd″, Stator resistanceShort circuit
StabilityStudy caseLoad P held as constant power, Load P held as constant current and the reactive power equivalentsStability simulation section of the study case (Ctrl+,)
EMTNetworkFrequencyNetwork (nothing selected)
EMTExternal gridsShort-circuit power max, R/X ratio max, and the zero-sequence ratios for unbalanced faultsShort circuit
EMTMachinesSubtransient reactance xd″, Stator resistanceShort circuit
EMTLinesLength, Resistance R′, Reactance X′, Susceptance B′, and the zero-sequence values for unbalanced faultsBasic data, Short circuit
EMTTransformersVector group, neutral earthingBasic data, Short circuit

The table does not repeat what an earlier study needs. These rules cover the rest:

For the formulas behind each field, see the calculation engine.

Check your data